Table 3

Pre and post works DEAP energy rating and monitored − predicted results comparison, showing performance gap. Source TUDublin Author.

House Floor Area DEAP (excludes cooking & appliances) Air Permeability Monitored* Notes
m2 BER kWh/yr kWh/m2/yr kWh/yr kWh/m2/yr
A (HP) Pre Works 79.42 B2 9,317 117.31 0.38 ach Q50 7.6 5,066 64 *Excl Room Stove
Predicted* *incl 4 months post works monitored
Post Works* 79.42 A2 2,610 32.86 0.41 ach Q50 8.23 3,987 50 *Excl Room Stove,
Floor Area DEAP Air Permeability Monitored* Notes
BER kWh/yr kWh/m2/yr kWh/yr kWh/m2/yr
B (Attic Conv) Pre Works 90.25 E2 31,620 350.36 0.62 ach Q50 12.4 11,930 132 *Elec from Bills, Heat Monitored+Calc
Predicted* only 4 months monitored
Post Works* 90.25 B1 7,576 83,94 0.5 ach *Q50 9.94 4,800 53 *Elec and Heat Monitored